尤物视频污,99热99热99超碰,精品久久久久女少妇,少妇精品无码,日B视屏久久香色,亚洲美女午夜福利av,国产美女被操,国产九九精品,国产久久色情

China SPR-YP21E SPR-YC21 Micro Differential Pressure Manual Controller Installation Location - China Supplier
China SPR-YP21E SPR-YC21 Micro Differential Pressure Manual Controller Installation Location - China Supplier China SPR-YP21E SPR-YC21 Micro Differential Pressure Manual Controller Installation Location - China Supplier

SPR-YP21E SPR-YC21 Micro Differential Pressure Manual Controller Installation Location

Price:Negotiable
Industry Category:
Product Category:
Brand: 西安
Spec:


Contact Info
  • Add:陜西省西安市翠華路60號(hào), Zip:
  • Contact: 劉品宜
  • Tel:13572979371
  • Email:243616989@qq.com

Other Products

Description
Additional Information

Hospital ProjectAirflow Management SystemUsage Instructions

Introduction to the Airflow Management System:

The Airflow Management System is an integrated control device that regulates the pressure difference between adjacent spaces by controlling the exhaust and supply air ratio.

SPR-JK200YAirflow Management Main Unit

Designed for negative pressure isolation ward areas, it monitors and controls indoor air pressure difference, air volume, air velocity, valve status, fan operation, ward disinfection, audible and visual alarms, and fault display. Through real-time monitoring, it also performs integrated control of equipment operational status.

Working PrincipleThe Airflow Management Main Unit communicates with the Airflow Controller via a two-wire bus, collecting operational status from fans, manual controllers, micro differential pressure sensors, and electric actuators (exhaust/supply air valves). It provides audible and visual indications, records, and prints alarm or fault information. The main unit can supply nursing stations or duty room staff with alarm or fault location information from the airflow management system, enabling them to monitor system status and promptly address alarms or faults.

Installation LocationThe Airflow Management Main Unit is installed in nursing stations or duty rooms, using wall-mounted installation. [Note: One unit per nursing station or duty room is sufficient.]

For system configuration, product parameters, and pricing, please call our company.

Contact: Manager Liu

Phone: 13572979371 (same for WeChat — 135 7297 9371)

We wholeheartedly provide comprehensive solutions and product services!!!

SPR-ZK20EAirflow Controller

Used in negative pressure ward airflow management systems to control the start/stop and speed of supply and exhaust fans.

DefinitionThe Airflow Controller, also known as the Fan Controller, is used in negative pressure ward airflow management systems to control the start/stop and speed of exhaust/supply fans.

Application AreasNegative pressure wards, cleanrooms, pressurized air supply systems for anterooms and stairwells, garage exhaust systems, etc.

Working PrincipleThe Airflow Controller communicates with the integrated controller. Based on the operating mode set by the manual controller, it sequentially starts/stops exhaust/supply (supply/exhaust) fans and adjusts the frequency converter according to the opening ratio of exhaust/supply air valves to control fan speed via variable frequency.

Installation LocationThe Airflow Controller is installed in the fan distribution box, with a 1:1 ratio to fans. Each fan requires one Airflow Controller.

SPR-YP21E; SPR-YC21Micro Differential Pressure Manual Controller

Used in negative pressure ward airflow management systems to monitor and manually control indoor air pressure difference.

DefinitionThe Micro Differential Pressure Manual Controller is one of the main devices in the negative pressure ward airflow management system, used to monitor and manually control the air pressure difference inside and outside the ward.

Application AreasNegative pressure wards, cleanrooms, etc.

Working PrincipleThe Micro Differential Pressure Manual Controller, installed at the ward entrance, monitors and controls the relative pressure difference inside and outside the ward in real time. It features preset multiple operating modes, allowing automatic or manual control of air volume regulating valves (supply and exhaust air valves). In cleaning mode, it facilitates disinfection of the ward by staff after patient discharge.

Installation LocationAt the ward entrance, medical corridor, or buffer room, within visual range, at a height of approximately 1.5m to 1.6 meters.

Industry Category
Product Category
Brand: 西安
Spec:
Stock: 1000
Manufacturer:
Origin: China / Shaanxi / Xianshi
About Toocle.com - Partner Programme - Old Version
Copyright ? Toocle.com. All Rights Reserved.
(浙)-經(jīng)營性-2023-0192
ChatGlobal Chat Now 八宿县| 丽江市| 灵川县| 涟源市| 汪清县| 铜鼓县| 衡南县| 石嘴山市| 遂川县| 宁陕县| 遵义县| 黑河市| 合肥市| 沧州市| 遵义县| 射阳县| 石嘴山市| 南雄市| 大连市| 和静县| 麦盖提县| 理塘县| 新宁县| 中宁县| 定远县| 拉萨市| 象山县| 柘荣县| 麻栗坡县| 吉木萨尔县| 高台县| 丘北县| 略阳县| 教育| 城步| 鹤山市| 湖南省| 封开县| 武陟县| 青阳县| 涞水县|