Condensing gas boiler burner failure

Price:¥10000 /t
Industry Category: Machinery & Equipment/Electric Heating Equipment/Medium Frequency Power Supplies
Product Category:
Brand: 納德
Spec: ND-240


Contact Info
  • Add:湖北省天門市經(jīng)濟開發(fā)區(qū)緯五路以南、接官路以東300米, Zip: 431700
  • Contact: 范天煜
  • Tel:15271210888
  • Email:2381609225@qq.com

Other Products

Description
Additional Information

1. Power on, press start, motor does not rotate

     (1) Condensing gas boiler locked due to insufficient air pressure; adjust pressure to specified value.

     (2) Solenoid valve leaking, gas leakage at joints, check and lock; clean or repair solenoid valve pipe joints.

     (3) Thermal relay open circuit; reset and check for damaged components and motor current.

     (4) At least one condition in the circuit is not met (water level, pressure, temperature, and whether the programmer is powered on); check if water level, pressure, or temperature exceeds limits.

2. Condensing gas boiler pre-purge normal after startup, but ignition fails

     (1) Insufficient ignition gas supply, check circuit and repair.

     (2) Solenoid valve not working (main valve, ignition valve); replace.

     (3) Solenoid valve burnt out; replace.

     (4) Unstable air pressure; adjust pressure to specified value.

     (5) Excessive air volume; reduce air distribution and damper opening.

3. Condensing gas boiler fails to ignite, air pressure normal, power available but no spark

     (1) Ignition transformer burnt out; replace.

     (2) High-voltage line damaged or detached; reinstall or replace.

     (3) Gap too large or too small, incorrect ignition rod position; adjust position.

     (4) Electrode cracked or short-circuited to ground; reinstall or replace.

4. Condensing gas boiler flame extinguishes within 5 seconds after ignition

     (1) Insufficient air pressure, large pressure drop, low gas supply flow; readjust pressure, clean filter.

     (2) Air volume too low, incomplete combustion, thick smoke; adjust air volume.

     (3) Air volume too high, white gas appears; adjust air volume.

5. White smoke

     (1) Air volume too low; reduce damper opening.

     (2) Air humidity too high; appropriately reduce air volume, increase intake air temperature.

     (3) Low flue gas temperature; take measures to increase flue gas temperature.

6. Condensing gas boiler damper stops under control state

     Damper position switch signal not fed back to program signal; check if damper wiring is loose or switch is faulty.

7. Burner motor does not rotate

     (1) No voltage; connect circuit.

     (2) Fuse damaged; replace fuse.

     (3) Motor malfunction; repair.

     (4) Control circuit interrupted; locate breakpoint, connect or disconnect regulator or monitor.

     (5) Gas supply interrupted; open ball valve, notify gas authority if gas supply is insufficient for an extended period.

     (6) Control malfunction; replace.

     (7) Contactor not working; manually reset and test.

     (8) Thermal relay damaged; replace thermal relay.

8. Burner motor runs but stops after pre-purge

     (1) Air pressure switch malfunction; replace.

     (2) Pressure switch contaminated, pipe blocked; clean.

     (3) Solenoid valve not sealing; repair or replace solenoid valve.

9. Condensing gas boiler burner motor runs, voltage applied to controller terminal 16, no ignition, fault shutdown after a short time

     (1) Ignition electrode gap too large; adjust electrode spacing.

     (2) Contaminated; clean thoroughly.

     (3) Ignition electrode or circuit grounded; eliminate grounding, replace damaged electrode or cable.

     (4) Ignition transformer malfunction; replace ignition transformer.

10. Motor runs, ignition normal, but fault shutdown after a short time

     Solenoid valve did not open due to damaged coil or broken cable; replace solenoid valve or fix circuit break, check voltage at terminal 17.

Industry Category Machinery & Equipment/Electric Heating Equipment/Medium Frequency Power Supplies
Product Category
Brand: 納德
Spec: ND-240
Stock: 1000
Manufacturer:
Origin: China / Hubei / Tianmenshi
About Toocle.com - Partner Programme - Old Version
Copyright ? Toocle.com. All Rights Reserved.
(浙)-經(jīng)營性-2023-0192
ChatGlobal Chat Now 稻城县| 乌海市| 前郭尔| 南安市| 松溪县| 临洮县| 阳城县| 泌阳县| 汉中市| 秦安县| 小金县| 兴城市| 巧家县| 防城港市| 雷波县| 通道| 宁夏| 沁阳市| 金秀| 鸡东县| 封丘县| 宁明县| 岐山县| 准格尔旗| 五常市| 中西区| 甘洛县| 莱芜市| 宾阳县| 兴和县| 辽中县| 嵩明县| 兴海县| 民权县| 通榆县| 泰来县| 苗栗市| 潢川县| 进贤县| 辽宁省| 洪江市|